MITEL XRT-600
- Part Number: XRT600
- Category: General Purpose UPS
- Manufacturer: Para Systems, Inc
- Quantity: 3
The XRT series of Uninterruptible power supplies are based on an advanced true sinewave power system that filters and protects the electronic equipment from all types of power line problems. The various models provide from 600 VA to 2000 VA of power for voltage ranges of 120 VAC, 208 VAC and 240 VAC single phase 60 Hz. units, and 220 VAC through 240 VAC 50 Hz. units. At all power levels and voltage ranges the load is protected against AC line spikes, surges, dropouts, brownouts and blackouts. All 60 Hertz models include electrical isolation from the power line to the AC load. During operation, all of the critical parameters are continuously monitored. The parameters may be monitored at the UPS with an LED display on the XRT600, or with a sophisticated LCD display that contains 32 characters on the XRT1000 and larger units. In all models the communications port can be used with the Minuteman Sentry or PowerMon software to report all of the critical parameters as well as controlling the UPS's functions via remote control. Built in is the provision for a remote master Output Power OFF switch so that a user-upplied power down switch or relay can immediately shut off the output power.
The XRT series of UPS's are "Line-Interactive". That is, during normal operation from the AC line, the line AC is passed through an isolation transformer and filtering system that provides the maximum efficiency, safety and reliability. During normal AC operation, the incoming line voltage is continuously monitored and automatic correction is made for under-voltage or over-voltage conditions. This provides AC line correction for a range of 75% to 116% of the nominal line voltage. When these limits are exceeded, or if the line frequency varies more than plus or minus 3 Hertz, the unit automatically switches to battery power until normal AC is restored. In normal operation the battery is continuously charged so that full battery power is always available.
The XRT series of UPS's are "Line-Interactive". That is, during normal operation from the AC line, the line AC is passed through an isolation transformer and filtering system that provides the maximum efficiency, safety and reliability. During normal AC operation, the incoming line voltage is continuously monitored and automatic correction is made for under-voltage or over-voltage conditions. This provides AC line correction for a range of 75% to 116% of the nominal line voltage. When these limits are exceeded, or if the line frequency varies more than plus or minus 3 Hertz, the unit automatically switches to battery power until normal AC is restored. In normal operation the battery is continuously charged so that full battery power is always available.
Technical Information
Receptacles: 4 x NEMA 5-15RSwitching Time: 4 ms
Power Description
Load Capacity (VA): 600 VAInput Voltage: 110 V AC
Output Voltage: 120 V AC
Battery Information
Backup/Run Time (Full Load): 30 MinuteMaximum Battery Recharge Time: 4 Hour
Physical Characteristics
Height: 10"Width: 8.8"
Depth: 19.8"
Weight (Approximate): 61 lb